Here is a note for everyone: Put Temperature sensors on the right spots!
Temperature sensors should be placed at 5 locations (see pic. 5) in the CA room to ensure uniform temperature and air circulation throughout the room.
[1] Warmest spot
[2] Coldest spot
[3] Safety (optional)
[4] Defrosting
[5] Start/stop
Easy mistake is made by the position of the Start/Stop senser [5]. Many times, we see that this sensor is installed just under the cooler and above the fruit bin. This will cause a massive number of start pluses of the cooling system because of short cut of the air from air-cooler.
What to do:
A) Place sensor [5] minimum 75 cm under the air cooler.
B) Install a plastic flap under & beside the air cooler to the top of the first fruit bin (see pic. 6).